Tuesday, February 8, 2011
Whats wrong with this picture?
A Fire Alarm System installed and approved 6 months ago fails to operate during a fire.
WHY ?
The Answers will shock you.
Hard to believe but a brand new Fire alarm system can be installed completely wrong yet be tested and approved by the fire Inspector as properly working and installed. This also includes Sprinkler systems
So how can this be? It begins with the very way how we train or not even train individuals to install them and how we train the individuals who inspect them.
Even a small fire system of 20 devices should take approximately 2 hours to test and inspect everything correctly and a large system should take all day to up to 3 days to test. But it is rarely done this way.
Instead the fact the system is properly installed to code is left up to the person installing and programming it the lead technician who in too many cases does not have the correct training to even know he has not installed the system correctly.
So how does this happen in the first place?
It starts because Fire alarm Systems are complex and require the following of several major building code sections which includes NFPA 72 Fire Alarms and Signaling Systems. NFPA 70 National Electrical code IFC International fire Code which is part of the ICC International Code Commission which is followed in many states. The ADA The Americans with Disabilities Act. And local and state codes.
This means to be able to properly install a Fire System you need knowledge of all of them and to be taught all of them as they pertain to Fire Alarm systems, and unfortunately there is not one school or class which totally covers the complete installation of a fire system from conception to Finnish. To fully understand how to install and service fire systems you need the knowledge of being an electrician and an electronics technician. But
most learning is on the job from people who have not been trained properly to begin with.
Just because you know how to wire a smoke detector does not mean you know how to properly run wiring and conduit to meet the Electrical Code, and this is where the problem begins with most of the schools you sit in class and watch the presentation but the hands on skills are not tested it being instead lead up to the people in the field teaching it who in many cases are not doing it right to begin with.
So now you can have a tech or installer with every license and certification card in his pocket and every class he can take and still has absolutely no idea how to properly install a fire system. I see it every day.
For beginners
Not once in any fire alarm class I have ever attended was the National Electrical Codes for fire alarms ever discussed or shown so you can wire a system totally wrong and unless an Electrical Inspector has checked it for accuracy you will never know it and neither will the Fire Inspector. Fire alarms should have an Electrical Inspection by an Electrical Inspector to make sure all wiring and piping complies with code and then is followed up by a fire system inspection to insure devices work.
But it does not work this way. Then you have electrical inspectors who want nothing to do with fire systems also because they consider it low voltage, which is fewer than 50 volts. And so what you have is a bunch of people running around saying they are certified technicians with cards which are totally worthless.
I challenge any code making or certifying organization of fire alarms to prove me wrong.
Of course they never will because they know what I am writing is the truth.
So should only Electricians install and electronics’ techs service and program well that’s what many in the industry suggest because there are very few individuals like myself who are cross trained in both electrical and electronics.
I estimate up to as many as 70+ % of fire alarms systems are improperly installed .Based on what I have observed in the 30 + years of work experience I have working as a trouble shooter.
So what about the Fire Inspectors same thing there not electricians or techs they know how to pull a manual station and make sure horns sound but they do not have the knowledge to know what goes on inside the system unless they have taken an interest and been shown by some one like myself what to look for.
Only 2 times in 2 communities did I see a comprehensive inspection the one I live in Penn Hills and in Wilkinsburg Pa.
The other day I caught a very large mid regional integration company that used orange extension cord wire inside a wall to power a fire system at a residential facility for at risk youth and when the individuals who installed it came down with the installation manager he tried to tell me it was OK to use this type of wire. I then pulled out the NEC code book I keep in my truck and showed him why it was wrong and he tried to tell me since fire alarms are class II wiring systems Fire alarms do not follow NEC . Wrong.
But there you go the lead guy in charge of a multimillion dollar integration company who has no idea what he does are how to install a fire alarm yet they are installing every day in Schools, Malls, hospitals, colleges etc.
Feel safe I would not be.
There are so many things that can and do go wrong when Fire systems are installed it would curl your hair.
But until the tragedy happens and a full investigation is conducted it is too late.
So what is the industry doing to make sure everyone is properly trained ? Not a dam thing.
So we keep turning out certified individuals who have absolutely no idea there installing incorrectly.
And leave it up to the courts and experts to fight it out when the lawsuits get filed.
What could be done to correct it.
To begin with incorporate all the extra codes sections you need into one code book instead of having to reference 5 different books and make the code readable at a 12th grade or lower level not in engineering language. And make the codes affordable. I would also insist on electrical inspections as well.
But of course until more people die nothing will be done and major court awards will continue.
In my next article I will talk about sprinkler systems and the total panacea for 100% public safety the fire service is trying to make them out for which they are not.
I will discuss a $4million dollar restaurant where a sprinkler system was inspected passed and then failed and $250,000. in damage resulted Sprinklers have big issues too.
And this is another case where a system never should have been passed and inspectors need to loose there jobs..
Where did the fire start?
By Nick Markowitz Jr.
I ran into an unusual situation the other day where a fire could have started but where investigators might easily miss the actual cause of the fire.
One of the services I provide to my alarm customers is keeping an eye on there properties during the winter when there closed. Several of my customers are in summer time business and or also are what we call Snow Birds up here where they like to take off for warmer climate areas during the winter.
Well one of these stores fronts I watch in the New Castle Pa. area sells swimming pools and the store is vacant all winter and heat is turned off and store winterized including putting a 120 vac electric heat tape around the water meter piping.
The owner calls me and asks me to check the store the other day because a contractor has some work to do in there as there getting ready for some remodeling and the heat did not come on correctly. No problem the next morning I head up there and when I walk into the store to shut off the burglar alarm I hear a loud hissing noise from the back. Yea I got a broken water pipe no doubt about it. Just what kind of mess was I going to find and do I have to cut power was my worry.
I look in the back storage room where I hear the leak and find that water is spraying a fine mist out just thru the main shut off valve onto both walls. One stroke of luck though is there is a floor drain catching most of it. The one bad thing is it is spraying directly on an electrical outlet where the heat tape is plugged in and I can smell something burning.
I quickly shut off power call 911 as I do not know who the water supplier for the store is but I will need them to shut it off at the street box. They notify Water Company for me and firefighters came to the store non emergency response and they helped me get the water under control till Water Company arrives.
We set up some dikes and eliminated the water spray on the walls.
The water Company arrives and luckily even with the snow on the ground they know where to look and quickly turn off the water.
Tragedy averted and only one room to clean up.
But what if I had not gotten there in time what if the water caused the outlet to catch fire
The walls where covered with dark paneling and there was a 7 foot ceiling Flexible Fiberglas drop in panels and a wooden deck above it used for storage the room measured aprox 8x8 feet .
If the outlet would have ignited the wall chances are the entire wall would burn down to the studs and just burnt copper wire and a box would be hanging with the extension cord plugged in.
So you arrive on scene and start the investigation it would look pretty conclusive the fire started at the outlet do to a malfunction the water running could be explained away by either the room getting hot enough to loosen solder on pipes and cause the leak or that a firefighter inadvertently damaged during attempts to put it out .
A forensic investigation of the valve might prove it was the culprit if it could be determined the damage was pre not post fire but only if you would run the scenario the piping was even involved because this is one of those fires where it would be very easy due to all the electrical activity at the outlet to say that’s where it started. Plus if the fire was basically kept to just that area how hard would it even be looked at when it appears obvious what happened.
This once again proves out that Fire Science and Investigation is not 100% perfect. And why as an investigator you must weigh all options. Or as in this case could happen the wrong party could be held liable.
Sunday, October 24, 2010
Fire Investigation and Junk Science
Wednesday, June 30, 2010
Dealing With Antique Fire Panel Power Issues
including the use of OSHA lock-out, tag-out procedures
Before there was a fire alarm manufacturing company by the name of FireLite, Silent Knight, etc., with panels which incorporated electronic components in them, there where companies known as Faraday, Auth, Autocall, Standard Time, Edwards, etc. These companies produced panels which ran strictly on 120/240 volts AC and used relays and big wire-wound resistors.
These panels made use of two separate power phases to the panel. If the primary phase would go out, the secondary phase would take over and sound a trouble bell or gong. Big, large AC series wired bells or horns were used in the system to sound the alarm. Some where steady while others pulsed a defined code.
These systems, while primitive next to modern panels, where the Cadillac of their day, however. They where built in big, heavy red or silver steel enclosures which contained large pieces of ½ inch or thicker slate, which the components where mounted to. Yes, they are now dinosaurs, but they where built to run forever. However, as technology has changed, so has the fire alarm industry.
These old panels, which used pull stations and heat detectors to activate them and had no smoke detectors or battery back up, have long past there usefulness. And yet there are still many of them out there in apartment buildings and town halls, even some schools.
As codes evolve in coming years these panels will need to be pulled out and replaced. The replacement of these panels carry with it a high risk of danger to technicians who are not familiar with how power was supplied. The problem starts at how they where wired into the 120/230 volt circuit in the building. This is because the small 30 or 60 Amp knife switch boxes that are wired to provide power to the panels are not fused or breaker protected, like normal knife switch boxes.
Fire alarm systems in those days where required to be wired ahead of the main switch gear so that even if the buildings main breaker was pulled, power was always maintained to the fire system. So when a technician pulls the 120 AC wiring out or they go to install 120 AC wiring in the knife switch box they’re dealing with danger should they make contact with the knife switch’s upper lug assembly.
If you will recall, these knife switches are not typically over current protected. Should a technician slip with a screwdriver, it will physically melt and explode instead of tripping the building’s main breaker. This is why only a qualified electrician should remove and remake the 120 volt connection to these knife switch boxes. The alternative is to plug off and abandon them and bring in a new circuit feed that is properly breaker protected.
OSHA lock-out, tag-out procedures must be utilized when working with these old switches because there is always the potential for the switch assembly to not move properly. There’s also the potential that it will not break, which means that 120 volts will continue to be maintained at the panel.
Technicians should carry and know how to properly use UL-Listed Category I or II, 120-volt AC testers, such as a properly used proximity tester or multi-meter to make sure power is fully off when operating one of these old knife switches. In fact, even when electricians and technicians work on modern breaker-controlled panels, they are by law required to follow OSHA Lock-Out, Tag-Out procedures.
If your technicians are not properly trained in the utilization of this procedure, the fines can be substantial should an accident occur. One single violation of OSHA Lock-Out, Tag-Out can result in a fine of $15,000.00!
Alarm companies may think they are exempt from OSHA, but they are just as responsible as a company with a hundred employees. Not even a one-man shop is exempt from these rules. They must understand and be able to fully implement the safety rules and regulations of OSHA or they operate at their own peril.
Yes, these old AC fire systems bring a lot of laughs and nostalgia and the old slate control boards make neat discussion pieces in the den or office, but they can also kill when not properly handled, so follow the rules and you’ll live to laugh another day.
Wednesday, June 9, 2010
Don't Forget That Little Green Wire

it really does nothing and doesn't need
hooked up, right?
WRONG!
A fire alarm system is sounding its trouble signal in a commercial building and the maintenance man has summoned me to check it. He pulls out his ring of keys, inserts them into the lock, then quite suddenly he's unable to move--he is frozen in place.
What exactly has happened here do you suppose?
Well, it's my guess that he's received an electrical shock. Luckily, this time he manages to pull away, but a few seconds more and he could have been toast. So what happened?
It appears the people who installed the fire alarm panel did not do their job properly as they forgot or simply failed to install a small green bonding jumper from the removable panel lid to the back box. This allowed electrical current to flow through the lid when the hot 120 volt wire supplying power to the panel pulled loose, coming in contact with the lid.
Now, had this jumper been bonded from lid to back box, and if the panel had been grounded properly, this event would not have taken place. The breaker would have tripped out and just the trouble signal would have sounded. The problem would have been spotted as soon as the lid was opened. Instead, because the jumper was not used, the maintenance man got a severe jolt.
Grounding and bonding of electrical equipment is critical to assuring that it operates properly. It also assures that any type of overload is cleared. It also assures that if a wire or component disintegrates and touches the metal enclosure in the system, nothing bad will happen to someone working on it.
Now, here's the kicker, not all lids need to be grounded. This is especially true if it is permanently attached to the panel box by means of a full-length piano-type hinge. In this case, code considers the lid properly bonded due to the continual path of metal touching. This is not something you have with a removable lid where only 2 small areas of the lid touch the panel box.
You say "bonding and grounding, what's the difference?"
Bonding is used to eliminate a possible hazard, like with the removable lid. The back box has a ground wire which runs the entire way back to the main service entrance for power. I know it's confusing, but follow the manufacture's guide lines and you'll do just fine. But if you fail to follow them, sooner or later something will fail and there will either be a fire or someone will get shocked.
With electricity it's just like a chain... the weakest link is where the problem will develop.
Wednesday, May 26, 2010
West Coast manufactuers learn hard lessons
| You would expect a machine from Europe to not work the same and require modification To be able to be used in the USA But would you expect the same thing when a West Coast machine is installed on the East Coast? As a trouble shooting electrician I often get called upon to hook up and commission machinery a customer may have bought either 2nd hand or from a country other then the USA and of course you would expect issues when it comes to making everything compatible and working as foreign countries often use different power systems than we do here in America. For example our traditional power system to a home is 120/230 60 Hz while in Europe it is 230 50Hz they supply to homes and business. This can be overcome several different ways and as long as all the rules of electricity is followed different machines from different countries can run with no problems. With this thought in mine you would think that when you buy a machine or system here in the USA it would work just as well in California as it would in Florida or Pennsylvania but this is not always the case. Take the gate system one of my clients bought to use with his mini storage facility. It was installed in may and ran fine all summer long but when it started getting cold in October and then temperatures plunged in November the gate started acting up. After some investigation it was determined that the gate manufacturer was using a active IR beam system that was designed to make the gate stop and reverse should a child or object be under the gate when it closes an excellent safety control but however fatally flawed. The active IR beam was only meant to be used in climates where it is above 32 F And in November in Pittsburgh it often goes well below 32F at night. Thus the problem, when the gate manufacturer was contacted about the problem and it gets so cold here they seemed surprised. Supposedly they tested the gate to 0 F and had no problems. But then again that was in a lab not Pittsburgh with wild temperature swings daily some times the end result the beam needed changed to a beefed up unit. which could handle the cold. Now a manufacturer that makes a product that is supposed to be able to be used any where in the USA you think would do the research and field testing before sending out a product but this is apparently not the case as I hit this problem all the time. Take the Burglar Alarm panel a manufacturer from Oregon was selling in the Pittsburgh area in early 80's These panels had all kinds of great new features but had continual problems of causing false alarms and arming and disarming by themselves. The problem was ultimately found to be that while the panels worked fine on the West Coast where they have good clean electrical power where when they say an outlet is providing 120 volts it actually is . But on the east coast the power is not as clean and as solid some times only 108 might be coming out of an outlet the result the panels advanced microprocessors could not withstand the imbalance and problems developed. To make the panels work properly you needed a filtered /regulated power supply transformer and the panel worked great only problem these transformers at the time cost as much or more than the panel cost. End result they stopped selling product on the east coast where bought and sold several times and are out of business. So then you have to ask your self where was the research and development at with these products? Well apparently there was none. What they should have done is send units out to various parts of the country for what is known as Beta Testing . This is where Alarm dealers like myself test the equipment in the filed to discover if there are problems. Honeywell Security does this and I participate as one of there testers and often times we find problems not encountered in the lab and it provides positive feedback To Honeywell so that they do provide a superior tested out product before releasing it for general sale. Sure these programs cost money and can be a pain to run but in the long run it saves money and face. So why are more companies not doing it? It comes down to the same old thing everything comes down to Money and incompetence. This is just one of many reasons why when companies try to expand and go national or world wide they often fail .Because they do not put enough money into research and development and it comes back to bite them. It's the old story" Plan your work- work your Plan " " or fail to plan –plan to fail. |
Monday, May 24, 2010
Home Sprinkler Advocate Voices Opposite Opinion
---- by Eric T. McMullen ----
Monday, May 24, 2010, 11:05 AM
Mr. Markowitz,
I was reading your Blog titled “Things they do not tell you about home fire sprinkler systems” http://nickmarkowitz.blogspot.com/2010/04/things-they-do-not-tell-you-about-home.html and felt compelled to contact you to challenge some of your assertions about fire sprinklers. My computer system at work does not allow me to post a comment directly to your blog, so I thought I’d send you an email.
I will attempt to address your comments in the order you made them;
You mentioned needed a “good” city water pressure, and while good may be a relative term, a residential fire sprinkler system can be designed for pressures as low as 7 psi. I don’t know of many, if any, municipal water supplies that can’t provided 7 psi.
Your point about connection to the water main is valid in many areas. In Oregon, multipurpose systems are allowed to be connected directly to the potable water system. In the case of multipurpose systems, there are no stagnant water issues and no backflow preventer or vacuum breaker requirements. The additional cost of systems development charges and standby fees is a problem, we are attempting to alleviate this problem in Oregon through legislation that will prevent the additional charges and fees on fire sprinkler systems in one- and two-family dwellings.
Your comments about homeowners insurance are just flat wrong and have been for some time now. Many years ago, there were some insurance companies that actually charged more when fire sprinklers were installed, but that Neanderthal way of thinking has long since passed. Every major insurance carrier in the Oregon currently offers discounts for fire sprinklers in one- and two-family dwellings. Insurance companies came to the realization that the amount of damage done by fire sprinkler systems pales in comparison to the damage done by fire, smoke and heat. Scottsdale, AZ has had a fire sprinkler ordinance in place since 1986 and their data indicates losses dues to fire in sprinklered homes averaged $1,945 compared to $17,067 in non-sprinklered homes.
Your estimates on using a well as a water source are quite a bit high, Talco offers a pump and tank package for NFPA 13D systems at a cost of $2,200. The size of the home will not double or triple the cost of the pump and tank, it may increase the size of the tank by 40 or 50 gallons, but that won’t increase the cost much. In many cases, if the well has the capacity, the system can be designed to use the well pump to supply the fire sprinklers and the well casing and recovery rate to satisfy the stored water requirements. I can design a system with flow demands as low as 16 gpm at 7 psi, which many wells can supply.
As far as cold weather and freeze mitigation goes, dry and antifreeze systems are not practical for one- and two-family dwellings for many of the reasons you state, however the standard does allow them. There are practical approaches outlined in the standard to deal with freeze problems in wet systems. While the insulation can be moved, one can make the same case for any water pipes in your home. A fire sprinkler system, installed correctly, has no higher chance of freezing than any other domestic water pipe.
With regard to maintenance, there are practically no maintenance requirements for NFPA 13D systems, and certainly no mandate in the standard to pay a fee or have a third-party inspector do an annual service on the system. Multipurpose systems that are connected to the potable water system need the same maintenance as the other water pipes in your home, which for most folks, is none.
Accidental discharge of a fire sprinkler head is around 1 in 16 million and accidental leaks of the piping are no more common than potable water piping. The story you relayed about the accidental discharge due to a microwave oven is highly suspect. The lowest temperature sprinkler head is 135 degrees Fahrenheit and I find it very hard to believe that kind of heat could escape from a microwave and make it to the ceiling level without dissipating, unless the contents inside the microwave were actually on fire. If you can provide me the actual fire report showing otherwise, I will stand corrected.
Yes, residential sprinkler heads have been recalled, so have coffee makers, laptop batteries, Toyota vehicles…….product issue arise from time to time, it doesn’t mean we abandon a sensible idea because of one recall.
The fire service has never advocated for fire sprinklers only, we have always educated people on the need for both smoke alarms and fire sprinklers as a package together, your chance of survival with both rises exponentially.
In closing, I must say that I am surprised that your blog professes to be about fire and electrical safety, yet you attempt to derail one of the most effective tools we have to guard against dying in a fire in our homes. I have to wonder if, as a master electrician, you feel the same way about GFCIs or Arc Fault protection in our homes?
Regards, Eric T. McMullen
Assistant Chief ~ Fire Marshal
McMinnville Fire Department
McMinnville, OR
---- And my reply ----
Date: Monday, May 24, 2010, 8:21 PM
Thanks for the comments.
Working [water] pressures here in my community are very low where on the tops of hills and people who have opted for systems have had to install tanks per the sprinkler installers. Maybe the installers are wrong or just selling more than needed. Part of the problem is you must be a licensed master plumber to install them in Allegheny County. That's why the [high] cost. This is also a big union area, again [it's] why the costs are so high.
The insurance thing is for real here. [I] had a customer install sprinklers 3 years ago and his premiums went up when he notified his carrier he installed them. Maybe in your part of [the] country, since you have codes in place, they behave themselves, but not here, yet. Maybe once it is state wide they will level out.
As far as microwave going off and causing the damage, I have the pictures. Remember again this was in college housing.
As far as leaks, 6 - 10 residential systems I know customers have in their homes have leaked or frozen up. It is the nature of the weather cycle around here. We're up [and] down all winter and it affects things in ways you would not believe, unless you saw it with your own eyes. We can be 3 degree in morning and 38 by lunch, then back down to zero overnight.
[Regarding] installation issues, I am constantly responding to sprinkler system issues both commercial and residential, even in the summer. I just had a big fight with Penn Hills, Pa fire depts who refused to properly respond to a sprinkler call [where] $10,000 in damage happened.
Some areas over pressure is also a big problem. Just try and find an emergency restoration clean up crew or even a sprinkler crew available here during the winter when temps drop down below zero. I have had to wait 2-3 weeks to get [a] sprinkler company rep on site because of all the damage.
You should talk to Jack Mason, CFI Fire Marshal For Penn Hills and hear all his worries over this.
I have responded to 3 systems so far this year, commercial, where single heads went off for no reason at all.
I am not derailing sprinklers, I am just stating what I know can and does go wrong with them. If we are going to promote things, let's give both sides of the issue. All I hear from sprinkler advocates are rose colored glasses. What kind of backlash do you think is going to happen around here after the sprinklers are in and start popping because of installation issues. People are going to shut them off and ignore them just like the smoke detectors they take the battery's out of because they always false.
Take Anti-lock brakes, [the] greatest thing to come out, however they have killed hundreds who did not use them right, [those who] lifted their foot off [the] pedal when they applied them because they thought something was wrong.
I am glad things are working out over there in Oregon, but your dealing with issues there which are different here. I am not saying "do not put them in," but I am saying, "let's think things through before we mandate something that's going to come back and get us."
When the first person dies in a home with a sprinkler system because we have not explained exactly why and how something works, start expecting lawsuits and TV investigations.
-30-
Saturday, May 15, 2010
Things they do not tell you about home fire sprinkler systems
industry does not want to talk about--the
down side to residential fire protection sprinklers.
By Nick Markowitz Jr.
Ok, we have all heard the hype about just how effective sprinkler systems are in stopping dangerous Residential Fires and why they are needed in new home construction because of how light-weight the construction is0--and yes, this is all true. Sprinklers are one of the best ways to protect your family and loved ones, but they come with a lot of conditions that no one wants to talk about. So let's take a good look at sprinklers, things that can go wrong, and the true cost of implementation.
First problem is the water supply. Where you have good city water pressure you can do a house for around $2500.00, even less if you use standard PVC pipe instead of fire rated PVC, like Blaze Master. But this is where the problem begins.
Are you going to be allowed to take the sprinkler water off the house water main or will you have to put in a separate water main at the commercial water rate at an install cost of $5000.00? Also, will you have to install a special back flow preventer at $500.00, which requires annual inspections of $65.00, or perhaps a standard vacuum breaker at $20.00?
What about if you're not home and the system starts to discharge by accident? Will neighbors hear the bell or horn and call 911? Or will you need to have it monitored at $30.00 a month plus $1500.00 for the fire alarm monitoring panel.
Also, what about your homeowners insurance. Will it go down because you're making things safer? Nope! In fact, people who have installed sprinklers voluntarily in their homes have seen insurance rates double or more because of the potential for water damage!
But what if you do not have good water pressure, or let's say you have a well. All I can say is "Get ready to shell out another $5000.00!" This $5K will buy you a pressurized water tank in the ground. And if you have a really big home, the price can be double or even triple that!
We're just getting started here folks.
How about the cold winters some of us experience across the country. There are several ways to deal with this issue and each one has its good and bad points, just as we've found with commercial building sprinkler systems.
One system is known as a dry system where the pipes are filled with air, which holds a valve closed until a sprinkler head activates. When this occurs, the air leaves the piping which allows water to flow through the pipes. A small oil-less compressor is required to keep pressure constant in a dry-type system. This is because of the expansion and contraction of the pipes. You also need to keep the drip drum at the end of the piping emptied of condensate to prevent the drum from freezing and blowing off.
As we have found in commercial buildings, these compressors lose power, drums do not get emptied, and the first hard freeze sends water everywhere. While dry systems work excellently when maintained properly, when they're not, they can cause a good bit of misery.
Then there is the option to add additional insulation in and around pipes to prevent freezing, and though this also works, any movement of the insulation by repair people, kids in the attic, etc., can leave the pipes vulnerable if not properly replaced. Again this works well but maintenance is the key.
Still another option is to use special antifreeze in the pipes. This works well but as they found out in one California residential community where a sprinkler company mixed its own antifreeze, it came out of the pipes during a kitchen fire and when it mixed with the hot cooking oil it exploded. This resulted in the death of a middle aged woman, which brings us to another subject. The sprinkler Industry says "There has never been a multiple fatality in a fully-sprinkled structure where a sprinkler system has been properly installed and maintained."
Well, guess what. Properly maintained means another fee... so expect to pay $150.00 annually for a sprinkler system test and hope you get a company that will actually do a proper test. For that matter, hope you get a contractor who properly installs your sprinkler system in the first place because overnight every Tom, Dick, and Harry will suddenly be in the sprinkler business.
Then, of course, what about when the sprinkler head does go off. Proponents of home sprinkler systems claim it will not be like the ones you see in movies... but they're not telling the whole truth either. Although residential heads are slower than commercial grade, they still put out a considerable amount of water.
I can personally attest to this where a Class R-13 residential sprinkler system was installed in college housing in California Pa., where there was not even a fire. All it was that triggered the incident was a blast of heat from a microwave oven when a student heated food wrong. A single sprinkler head destroyed the kitchen where all the drywall needed replaced. In addition, water leaked through to the room under it, destroying a ceiling. The total bill for this was approximately $8,000.00.
And yes, a sprinkler head and sprinkler piping can and will leak if pressure in the piping is accidentally increased by a faulty pressure regulator. This can also happen due to age as these systems deteriorate. It happens in commercial systems so why would it not in residential?
There has even been a massive sprinkler head recall by several manufacturers because of sprinkler heads that did not trip when there was a fire... and yes you can get false sprinkler alarms when pressure in piping changes. It happens in commercial buildings any time there's a major water break near by and water is turned back on later.
Something to also consider is why just not shut the system off after every one inspects and leaves? Yes you could do this but then again will the insurance company still be required to pay your claim because you shut the system off?
Also keep this in mind, when the first sprinkler systems where installed, it was done for property protection, not for human safety.
Sprinkler systems are by no means the 100% perfect answer. You could well have a properly maintained sprinkler system and still die in a fire in your home from smoke inhalation if the fire develops in the same room where you are located. A classic example would be a person who smokes in bed. A fire which starts in a bed will set off the sprinklers, but well after flames and or smoke have killed you. This is why it is important to still have and use smoke detectors.
So as you can see, all the hype about sprinklers you're hearing does not tell the downside. Over the next few years, you and the community you live in will have to deal with the politics associated with today's huge push for sprinklers in the home.